Rated heat output | Prated | kW | 29.3 | Seasonal space heating energy efficiency | ns | % | 112 |
Declared capacity for heating for part load at indoor | | | | Declared coefficient of performance or primary | | | |
|
temperature 20oC and outdoor temperature Tj | | | | energy ratio for part load at indoor temperature 20°C | | | |
|
| | | | and outdoor temperature Tj | | | |
Tj = -7°C | PdH | kW | 25.8 | Tj= -7°C | PERd | % | 97 |
Tj = +2°C | PdH | kW | 15.8 | Tj= +2°C | PERd | % | 121 |
Tj= +7°C | PdH | kW | 10.3 | Tj= +7°C | PERd | % | 118 |
Tj = +12°C | PdH | kW | 4.4 | Tj = +12°C | PERd | % | 112 |
Tj= bivalent temperature | PdH | kW | - | Tj= bivalent temperature | PERd | % | - |
Annual energy temperature | QHE | GJ | 195 | | | | |
Colder climate conditions | | | | | | |
Rated heat output | Prated | kW | 29.2 | Seasonal space heating energy efficiency | ns | % | 107 |
Declared capacity for heating for part load at indoor | | | | Declared coefficient of performance or primary |
|
temperature 20°C and outdoor temperature Tj | | | | energy ratio for part load at indoor temperature 20°C | |
|
| | | | and outdoor temperature Tj | | | |
Tj = -7°C | PdH | kW | 17.8 | Tj = -7°C | Pdh | kW | 108 |
Tj = +2°C | PdH | kW | 10.8 | Tj= +2°C | Pdh | kW | 117 |
Tj = +7°C | PdH | kW | 7 | Tj = +7°C | Pdh | kW | 112 |
Tj = +12°C | PdH | kW | 3.2 | Tj = +12°C | Pdh | % | 110 |
Tj = bivalent temperature | PdH | kW | - | Tj = bivalent temperature | PERd | % | - |
Tj = operation limit temperature | PdH | kW | 29.2 | Tj = operation limit temperature | PERd | % | 87 |
For air-to-water heat pumps: | PdH | kW | 23.9 | For air-to-water heat pumps: | PERd | % | 90 |
|
Tj = -15°C (if TOL= -20°C) | | | | Tj = -15°C (if TOL= -20°C) | | | |
Annual energy consumption | QHE | GJ | 242 | | | |
Warmer climate conditions | | | | | | | |
Rated heat output | Prated | kW | 35.9 | Seasonal space heating energy efficiency | ns | % | 115 |
Declared capacity for heating for part load at indoor | | | | Declared coefficient of performance or primary | | | |
|
temperature 20°C and outdoor temperature Tj | | | | energy ratio for part load at indoor temperature 20°C | | | |
|
| | | | and outdoor temperature Tj | | | |
Tj = +2°C | Pdh | kW | 35.9 | Tj = +2°C | PERd | kW | 118 |
Tj= +7°C | Pdh | kW | 23 | Tj = +7°C | PERd | kW | 121 |
Tj = +12°C | Pdh | kW | 10.4 | Tj = +12°C | PERd | kW | 116 |
Tj = bivalent temperature | Pdh | kW | - | Tj = bivalent temperature | PERd | % | - |
Annual energy consumption | QHE | GJ | 150 | | | |
Bivalent temperature | Tbiv | °C | TOL Tdesign | For air-to-water heat pumps | TOL | °C | -22 |
|
| | | | Operation limit temperature | WTOL | °C | 65 |
|
| | | | Heating water operation limit | | | |
Power consumption in modes other than active mode | | | |
Off mode | P (OFF) | kW | 0 | Rated heat output | Psup | KW | - |
Thermostat - off mode | P (TO) | kW | 0.021 | Type of energy input | Monovalent |
Standby mode | P (SB) | kW | 0.005 | | | | |
Cranksae heat mode | P (OK) | kW | - | | | |
Other items | | | | For air-to-water heat pumps | | | |
Capacity control | variable | | | Rated air flow rate outdoors | | m3/h | 10000 |
Sound power level, indoors/outdoors | L (WA) | dB | -75.3 | For water - or brine-to-water heat pumps | | | |
Emissions of nitrogen oxides | NOx | mg/kWh | 40 | Rated brine or water flow rate, | m3/h | | |
|
| | | | outdoor heat exchanger |
|